LINETRAXX® CEP410R-2

  • Forewarns developing earth faults
  • Response range from 10 mA to 30 A
  • Communicates via Modbus RTU
  • Enables remote condition monitoring
  • Compact, space saving design

The CEP410R residual current monitoring device is used to monitor the central earthing point.

This AC and pulsating DC sensitive monitoring device can be connected to existing communication networks, enabling remote condition monitoring. Two separately adjustable response values can be used to differentiate between pre-warning and main alarm (pre-warning = 50…100% of the set response value Idn).

The monitoring device is intended for monitoring at the central earthing point, for detecting PEN bridges and N conductor connections between separate TN systems.

Easy configuration via app

With the NFC function and the Bender Connect App you can easily configure the CEP410R via a smartphone.

Questions? Contact us!

CEP410R-2
  • Forewarns developing earth faults
  • Response range from 10 mA to 30 A
  • Communicates via Modbus RTU
  • Enables remote condition monitoring
  • Compact, space saving design

The CEP410R residual current monitoring device is used to monitor the central earthing point.

This AC and pulsating DC sensitive monitoring device can be connected to existing communication networks, enabling remote condition monitoring. Two separately adjustable response values can be used to differentiate between pre-warning and main alarm (pre-warning = 50…100% of the set response value Idn).

The monitoring device is intended for monitoring at the central earthing point, for detecting PEN bridges and N conductor connections between separate TN systems.

Easy configuration via app

With the NFC function and the Bender Connect App you can easily configure the CEP410R via a smartphone.

Questions? Contact us!

Features

  • AC and pulsed DC sensitive residual current monitor type A according to IEC 62020-1 
  • r.m.s. value measurement
  • Measuring range: 10 mA...30 A (42...70 Hz)
  • Prewarning: 50...100 % of the differential response current
  • Supply voltage DC 24 V or AC/DC 100…240 V 
  • LED strip measured value display
  • Adjustable response delay
  • One alarm relay (changeover contact)
  • N/C or N/O operation and fault memory behaviour selectable
  • RS-485 with Modbus RTU
  • Continuous measuring current transformer connection monitoring
  • NFC interface for configuration of the unit in energised and de-energised state

Applications

  • Monitoring of the central earthing point (CEP)
  • Detecting PEN bridges
  • Detecting N conductor connections between separate TN systems

LINETRAXX® CEP410R-2 Variant(s)

TypeSupply voltage USArt. No.
CEP410R-2DC 24 V; AC/DC 100…240 VB74603008

Optional Accessories for LINETRAXX® CEP410R-2

Accessories

TypeArt. No.
Sealable transparent cover (spare part)B80609199

External measuring current transformers

TypeInternal dimensions (mm)Art. No.
CTAC20ø 20B98110005
CTAC35ø 35B98110007
CTAC60ø 60B98110017
CTAC120ø 120B98110019
CTAC210ø 210B98110020
CTAS50ø 50B98110009
CTAS80ø 80B98110010
CTAS120ø 120B98110011
WR70x175S70 x 175 mmB911738
WR115x305S115 x 305 mmB911739
WR150x350S150 x 350 mmB911740
WR200x500S200 x 500 mmB911763
WR70x175SP70 x 175 mmB911790
WR115x305SP115 x 305 mmB911791
WR150x350SP150 x 350 mmB911792
WR200x500SP200 x 500 mmB911793

Downloads for LINETRAXX® CEP410R-2

NameCategorySizeLanguageTimestampD-/B-Number
CEP410R-2 Datasheets 4.9 MB DE2025/08/1212.08.2025D00527
CEP410R-2 Datasheets 4.9 MB EN2025/08/1212.08.2025D00527
CEP410R-2 Manuals 6.6 MB DE2025/08/1919.08.2025D00527
CEP410R-2 Manuals 6.6 MB EN2025/08/1919.08.2025D00527
CEP410R-2 Quickstarts 2.8 MB DE2025/08/0707.08.2025D00527
CEP410R-2 Quickstarts 2.8 MB EN2025/08/0707.08.2025D00527
CEP410 CE Declarations of conformity 86.2 KB 2025/06/1616.06.2025
UKCA - CEP410 Declarations of Conformity 167.3 KB 2025/06/1616.06.2025

Do you have any questions?

We will be happy to help you.

Contact form