LINETRAXX® CME420

The CME420 series current relays monitor undercurrent and overcurrent in AC systems as well as the current between two threshold values (window discriminator function). The currents are measured as r.m.s. values (AC). The currently measured value is continuously shown on the LC display. The measured value required to trigger the alarm relay is stored. Due to adjustable delay times, installation-specific characteristics, such as device-specific making currents, short-time current changes etc. can be considered. Current measurement is possible either directly or indirectly via standard current transformers (x/5 A). External supply voltage is required.

Questions? Contact us!

LINETRAXX® CME420
LINETRAXX® CME420

The CME420 series current relays monitor undercurrent and overcurrent in AC systems as well as the current between two threshold values (window discriminator function). The currents are measured as r.m.s. values (AC). The currently measured value is continuously shown on the LC display. The measured value required to trigger the alarm relay is stored. Due to adjustable delay times, installation-specific characteristics, such as device-specific making currents, short-time current changes etc. can be considered. Current measurement is possible either directly or indirectly via standard current transformers (x/5 A). External supply voltage is required.

Questions? Contact us!

Features

  • Undercurrent and overcurrent monitoring in AC systems 0.1…16 A
  • Indirect current monitoring with standard current transformers x/5 A
  • Transformation ratio n allows adaptation to all standard current transformers x/5 A
  • Different monitoring functions selectable < I, > I or < I/> I
  • Start-up delay, response delay, delay on release
  • Adjustable switching hysteresis
  • r.m.s. value measurement (AC)
  • Digital measured value display via multi-functional LC display
  • LEDs: Power On, Alarm 1, Alarm 2
  • Measured value memory for operating value
  • Continuous self monitoring
  • Internal test/reset button
  • Two separate alarm relays (one changeover contact each)
  • N/C or N/O operation and fault memory behaviour selectable
  • Password protection for device setting
  • Sealable transparent cover
  • Two-module enclosure (36 mm)
  • Push-wire terminal (two terminals per connection)
  • RoHS compliant

Applications

  • Current consumption of motors, such as pumps, elevators, cranes
  • Monitoring of lighting circuits, heating circuits, charging stations
  • Monitoring of emergency lighting
  • Monitoring of screw conveyors, e.g. in sewage plants
  • Dust removal in wood working

LINETRAXX® CME420 Variant(s)

TypeSupply voltage US*MeasurementDisplay rangeResponse valueArt. No.**
CME420-D-1DC 9.6…94 V/
AC 16…72 V,
42…460 Hz
directly/
via current transformer x/5A
0.1…16 A/
5…999 A
0.1…16 A x nB73060001
B93060001
CME420-D-2DC 70…300 V/
AC 70…300 V,
42…460 Hz
directly/
via current transformer x/5A
0.1…16 A/
5…999 A
0.1…16 A x nB73060002
B93060002

* absolute values
**(B7… = push-wire terminal / B9… = screw-type terminal)

Optional Accessories for LINETRAXX® CME420

TypeArt. No.
Mounting clip for screw mounting (one piece per device)B98060008
Mounting frame XM420B990994 

Downloads for LINETRAXX® CME420

NameCategorySizeLanguageTimestampD-/B-Number
UKCA - CME42x Declarations of Conformity 121.9 KB 2023/03/0606.03.2023
CME42x CE Declarations of conformity 89.0 KB 2023/02/1313.02.2023
CME420 Manuals 1.8 MB DE2020/09/1111.09.2020D00034
CME420 Manuals 1.5 MB EN2020/09/1111.09.2020D00034
CME420 Manuals 613.4 KB FR2019/05/1313.05.2019D00034
CME420 Datasheets 351.9 KB DE2019/05/1313.05.2019D00034
CME420 Datasheets 301.5 KB EN2019/05/1313.05.2019D00034
CME420 Datasheets 330.6 KB ES2019/05/1313.05.2019D00034
XM420-Schnittstellenoptionen Datasheets 264.1 KB DE2019/05/1313.05.2019
XM420 interface options Datasheets 223.5 KB EN2019/05/1313.05.2019D00051
CME420 Datasheets 286.0 KB FR2019/05/1313.05.2019D00034
Changed variants of relays from goldplated to silver-plated contacts Technical information 166.3 KB EN2022/06/2727.06.2022
Geänderte Relaisvarianten von vergoldeten Kontakten auf versilberte Kontakte Technical information 166.3 KB DE2022/06/2727.06.2022