en
Global - english
Sun Nov 19 22:31:53 2017
Sun Nov 19 22:31:54 2017
ISOMETER® isoPV1685RTU/isoPV1685P/isoPV1685PFR

ISOMETER® isoPV1685RTU/isoPV1685P/isoPV1685PFR

  • Insulation monitoring device for DC IT systems
  • Application photovoltaic systems up to DC 1500 V
  • Separately adjustable response values 200 Ω…1 MΩ
  • Automatic adaptation to the system leakage capacitance up to 2000 μF
  • Interface selectable RS-485 or Modbus

The device is used for insulation and residual current monitoring of large photovoltaic systems up to 1500 V designed as IT systems. The measurement method specially developed for slow voltage fluctuations (MPP-Tracking) monitors the insulation resistance even in systems equipped with large solar generator panels where extremely high system leakage capacitances against earth exist due to interference suppression methods. Adaptation to system-related high leakage capacitances also occurs automatically.

The device generates locating current pulses required for insulation fault location. That allows the localisation of the insulation fault using permanently installed or mobile insulation fault locators. Integrated residual current monitoring allows fast signalling of a measured insulation faults on the AC side (inverter, transformer).

  • Features
  • Applications
  • Accessories
  • Ordering information
  • Downloads
  • Only device versions isoPV1685PFR and isoPV1685P provide a locating current injector. The device version isoPV1685PFR additionally provides residual current monitoring!
  • Insulation monitoring of large-scale photovoltaic systems
  • Measurement of low-resistance insulation faults
  • Separately adjustable response values Ran1 (Alarm 1) and Ran2 (Alarm 2) (both 200 Ω…1 MΩ) for prewarning and alarm. Ran1 ≥ Ran2 applies.
  • Automatic adjustment to high system leakage capacitances up to 2000 μF, selectable range
  • Connection monitoring of L+, L- for reverse polarity
  • Integrated locating current injector up to 50 mA (isoPV1685P(FR) only)
  • Fast detection of insulation faults on the AC side by residual current monitoring (inverter, transformer) allowing fast disconnection (isoPV1685PFR only)
  • Residual current response values IΔn for prewarning and alarm (1…5 A) (isoPV1685PFR only)
  • CT connection monitoring (isoPV1685PFR only)
  • Device self test with automatic fault message in the event of a fault
  • Alarm relays separately adjustable for insulation faults, residual current faults and device errors (isoPV1685PFR only);
  • Alarm relays separately adjustable for insulation fault 1, insulation fault 2 (isoPV1685P, isoPV1685RTU only)
  • CAN interface to output measured values, statuses and alarms
  • RS-485 interface
    - isoPV1685(P)FR: BMS bus, e.g. to control the insulation fault location
    - isoPV1685RTU: BMS bus or Modbus (can be switched using the DIP switch)
  • μSD card with data logger and history memory for alarms

 

Variants of ISOMETER® isoPV1685RTU/isoPV1685P/isoPV1685PFR

Ordering information
TypeResponse value rangeSupply voltage*Art. No.
isoPV1685RTU-425200 Ω…1 MΩDC 18…30 VB91065603
isoPV1685P-425200 Ω…1 MΩDC 18…30 VB91065604
isoPV1685PFR-425200 Ω…1 MΩDC 18…30 VB91065600

Downloads for ISOMETER® isoPV1685RTU/isoPV1685P/isoPV1685PFR

Category

Language

Category Product Language Date Size Download